I'm gaffing a small film that takes place in a boatyard, on docks, and on day fishing boats for the most part. On our first few days on location, we tried using HMIs to maintain continuity when the sun went behind a cloud, but couldn't get them to work on the dock power. We first tried using an Arri 1800W Baby Max on the 20A dock receptacles but breakers kept tripping on the circuits. We next tried a 1200 Par. The breaker didn't trip, but the GFCI kept tripping. Why do HMIs trip GFCIs? It doesn't matter, because while the 1200 was up, we found it just didn't have the output we needed. What we need is a 4k Par, but the docks and boats don't have the service for it and we don't have the budget or man power to run feeder back to a generator on shore. I could operate the 4k at 240V on a Honda EU6500, but how do I get the ground fault protection we need shooting on or around the water? And do I need to ground the generator? If I do, how can I do it without running ground cable to shore? Any help would be greatly appreciated as we are in the midst of production and are scheduled to go back out on the docks and boats soon.
Isabelle Landers, Gaffer, Nashua, NH